A generlized correlation for refrigerant mass flow rate through adiabatic capillary tubes

  • Jongmin Choi
  • , Yongchan Kim*
  • , Ho Young Kim
  • *Corresponding author for this work

    Research output: Contribution to journalArticlepeer-review

    Abstract

    A capillary tube is a common expansion device used in small sized refrigeration and air-conditioning systems. A generalized correlation for refrigerant flow rate in adiabatic capillary tubes is developed by implementing dimensionless parameters based on extensive experimental data for R-22, R-290, and R-407C measured in this study. Dimensionless parameters are derived from the Buckingham Pi theorem, considering the effects of tube inlet conditions, capillary tube geometry, and refrigerant properties on mass flow rate. The generalized correlation yields good agreement with the present data for R-22, R-290, and R-407C with average and standard deviations of 0.9 and 5.0%, respectively. Approximately 97% of the present data are correlated within a relative deviation of ±10%. Further assessments of the correlation are made by comparing the predictions with measured data for R-12, R-134a, R-152a, R-410A, and R-600a in the open literature. The correlation predicts the data for those five refrigerants with average and standard deviations of -0.73 and 6.16%, respectively.

    Original languageEnglish
    Pages (from-to)881-888
    Number of pages8
    JournalInternational Journal of Refrigeration
    Volume26
    Issue number8
    DOIs
    Publication statusPublished - 2003 Dec

    Keywords

    • Air conditioner
    • Capillary tube
    • Domestic refrigerator
    • Expansion device
    • Flow
    • R-22
    • R-290
    • R-407C
    • Refrigerant
    • Simulation

    ASJC Scopus subject areas

    • Building and Construction
    • Mechanical Engineering

    Fingerprint

    Dive into the research topics of 'A generlized correlation for refrigerant mass flow rate through adiabatic capillary tubes'. Together they form a unique fingerprint.

    Cite this