Abstract
The KSTAR system, which includes a large amount of nonlinear load, is a relatively high reactive power consumption load which injects harmonic currents into the power system which could result in the possibility for a power system perturbation to occur in the transmission lines, affecting nearby customers. In order to maintain the power quality and power factor in the inner system of the KSTAR system and the adjacent distribution lines, the assessment of the effect of the DC power supply in the KSTAR system is required for appropriate countermeasures to be put in place. In this paper, on the basis of a preliminary inspection of the power system near a KSTAR system, the simulation of a compensating device is performed for the prevention of abnormal voltage variations caused by a large amount of reactive and nonlinear load. In addition, through the comparison of the pre- and post-application of compensation devices in the actual power system, it is verified that a stable operation of the KSTAR nuclear fusion experimental system can be achieved.
Original language | English |
---|---|
Pages (from-to) | 373-380 |
Number of pages | 8 |
Journal | Fusion Engineering and Design |
Volume | 86 |
Issue number | 4-5 |
DOIs | |
Publication status | Published - 2011 Jun |