Fault current constrained decentralized optimal power flow incorporating superconducting fault current limiter (SFCL)

Guk Hyun Moon, Young Min Wi, Kisung Lee, Sung Kwan Joo

Research output: Contribution to journalArticlepeer-review

18 Citations (Scopus)

Abstract

The addition of new generation capacity increases the fault current levels in power systems. New generation and transmission capacity additions can be limited by the fault current constraints in power systems. The superconducting fault current limiter (SFCL) has great potential as a special protection device to limit the fault current in the event of a fault in power systems. Installations of SFCLs can alter fault current levels in power systems, thereby influencing the power system planning. This paper presents fault current constrained decentralized optimal power flow (OPF) for generation system planning incorporating a SFCL. The numerical simulation results are presented to show the effectiveness of the proposed method.

Original languageEnglish
Article number5672804
Pages (from-to)2157-2160
Number of pages4
JournalIEEE Transactions on Applied Superconductivity
Volume21
Issue number3 PART 2
DOIs
Publication statusPublished - 2011 Jun

Bibliographical note

Funding Information:
Manuscript received August 03, 2010; accepted October 29, 2010. Date of publication December 23, 2010; date of current version May 27, 2011. This research was supported by Basic Science Research Program through the National Research Foundation of Korea (NRF) funded by the Ministry of Education, Science and Technology (2010-0006346).

Keywords

  • Decentralized optimal power flow
  • Fault current constraint
  • Power system planning
  • Superconducting fault current limiter
  • System studies for superconducting devices

ASJC Scopus subject areas

  • Electronic, Optical and Magnetic Materials
  • Condensed Matter Physics
  • Electrical and Electronic Engineering

Fingerprint

Dive into the research topics of 'Fault current constrained decentralized optimal power flow incorporating superconducting fault current limiter (SFCL)'. Together they form a unique fingerprint.

Cite this