Abstract
In this study, single-phase H2O/LiBr solution heat transfer and frictional pressure drop characteristics in plate heat exchangers (PHEs) with two different chevron angles are experimentally evaluated for triple-effect H2O/LiBr absorption chiller applications. The test PHEs are single-pass exchangers with 20 plates. Chevron angles are 78.5° and 55.7° for high- and low-theta PHEs, respectively. Heat transfer and frictional pressure drop experiments in the PHEs were conducted with LiBr concentration ranging from 50.21% to 64.92% (which is the widest concentration range for triple-effect absorption application), solution Reynolds number from 19.39 to 479.10, and Prandtl number from 3.63 to 24.40. All experiments were conducted within a ± 3% energy balance error range, and the heat transfer and frictional pressure drop correlations are developed and applicable within ± 14% and ± 6% error ranges, respectively, by considering the effect of the chevron angle. The correlations developed in this study are compared with correlations from literature. Finally, it is found that the chevron angle of the PHE does not give a significant effect on the energy savings.
Original language | English |
---|---|
Article number | 116730 |
Journal | Applied Thermal Engineering |
Volume | 189 |
DOIs | |
Publication status | Published - 2021 May 5 |
Bibliographical note
Publisher Copyright:© 2021 Elsevier Ltd
Keywords
- Energy performance parameter
- Frictional pressure drop
- HO/LiBr solution
- Heat transfer coefficient
- LiBr concentration
- Plate heat exchanger
ASJC Scopus subject areas
- Mechanical Engineering
- Energy Engineering and Power Technology
- Fluid Flow and Transfer Processes
- Industrial and Manufacturing Engineering