TY - GEN
T1 - New HVDC interaction between AC network and HVDC shunt reactor on Jeju converter station
AU - Kim, Chan Ki
AU - Kwon, Young Hun
AU - Jang, Gilsoo
PY - 2007
Y1 - 2007
N2 - This paper deals with a new HVDC interaction which was observed in the Jeju-Haenam HVDC system. The interaction is not from a system malfunction or controller loop problem but from the change of AC network scheme and the network operating condition. We have found that the interaction is caused by the voltage oscillation between the synchronous compensator and HVDC shunt reactor. We analyzed the cause of the interaction and suggested a solution.
AB - This paper deals with a new HVDC interaction which was observed in the Jeju-Haenam HVDC system. The interaction is not from a system malfunction or controller loop problem but from the change of AC network scheme and the network operating condition. We have found that the interaction is caused by the voltage oscillation between the synchronous compensator and HVDC shunt reactor. We analyzed the cause of the interaction and suggested a solution.
UR - http://www.scopus.com/inward/record.url?scp=42549127234&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=42549127234&partnerID=8YFLogxK
U2 - 10.1109/PES.2007.386068
DO - 10.1109/PES.2007.386068
M3 - Conference contribution
AN - SCOPUS:42549127234
SN - 1424412986
SN - 9781424412983
T3 - 2007 IEEE Power Engineering Society General Meeting, PES
BT - 2007 IEEE Power Engineering Society General Meeting, PES
T2 - 2007 IEEE Power Engineering Society General Meeting, PES
Y2 - 24 June 2007 through 28 June 2007
ER -