Protective relay system for the first demonstration of the HTS cable and the SFCL in live grid in Korea

Seung Ryul Lee, Jaeyoung Yoon, Byeong Mo Yang, Byongjun Lee

Research output: Contribution to journalArticlepeer-review

3 Citations (Scopus)

Abstract

This study proposed a novel power protection system for the application of 22.9 kV HTS cable and SFCL systems to the Icheon substation in South Korea, and studied the protective coordination of the proposed system using a transient simulation program, PSCAD/EMTDC. Korea Electric Power Cooperation (KEPCO) designed and reconstructed the protection system of the Icheon substation based on the results of this study. The 22.9 kV, 50 MVA HTS cable and 22.9 kV, 630 A hybrid SFCL systems have been successfully operated in the live power grid of the Icheon substation since August, 2011.

Original languageEnglish
Pages (from-to)286-291
Number of pages6
JournalPhysica C: Superconductivity and its Applications
Volume494
DOIs
Publication statusPublished - 2013

Keywords

  • HTS cable
  • Power system
  • Protection system
  • Protective relay
  • SFCL

ASJC Scopus subject areas

  • Electronic, Optical and Magnetic Materials
  • Condensed Matter Physics
  • Energy Engineering and Power Technology
  • Electrical and Electronic Engineering

Fingerprint

Dive into the research topics of 'Protective relay system for the first demonstration of the HTS cable and the SFCL in live grid in Korea'. Together they form a unique fingerprint.

Cite this